Your browser doesn't support javascript.
loading
Mostrar: 20 | 50 | 100
Resultados 1 - 1 de 1
Filtrar
Mais filtros










Base de dados
Intervalo de ano de publicação
1.
Infect Control Hosp Epidemiol ; 37(12): 1475-1480, 2016 12.
Artigo em Inglês | MEDLINE | ID: mdl-27640674

RESUMO

OBJECTIVE To determine the source of a Legionella pneumophila serogroup 5 nosocomial outbreak and the role of the heat exchanger installed on the hot water system within the previous year. SETTING A 400-bed tertiary care university hospital in Sherbrooke, Canada. METHODS Hot water samples were collected and cultured for L. pneumophila from 25 taps (baths and sinks) within wing A and 9 taps in wing B. Biofilm (5) and 2 L water samples (3) were collected within the heat exchangers for L. pneumophila culture and detection of protists. Sequence-based typing was performed on strain DNA extracts and pulsed-field gel electrophoresis patterns were analyzed. RESULTS Following 2 cases of hospital-acquired legionellosis, the hot water system investigation revealed a large proportion of L. pneumophila serogroup 5 positive taps (22/25 in wing A and 5/9 in wing B). High positivity was also detected in the heat exchanger of wing A in water samples (3/3) and swabs from the heat exchanger (4/5). The outbreak genotyping investigation identified the hot water system as the source of infections. Genotyping results revealed that all isolated environmental strains harbored the same related pulsed-field gel electrophoresis pattern and sequence-based type. CONCLUSIONS Two cases of hospital-acquired legionellosis occurred in the year following the installation of a heat exchanger to preheat hospital hot water. No cases were reported previously, although the same L. pneumophila strain was isolated from the hot water system in 1995. The heat exchanger promoted L. pneumophila growth and may have contributed to confirmed clinical cases. Infect. Control Hosp. Epidemiol. 2016;1475-1480.


Assuntos
Infecção Hospitalar/microbiologia , Infecção Hospitalar/transmissão , Temperatura Alta/efeitos adversos , Legionella pneumophila/isolamento & purificação , Doença dos Legionários/transmissão , Microbiologia da Água , Canadá , Conservação de Recursos Energéticos/métodos , Surtos de Doenças , Eletroforese em Gel de Campo Pulsado , Ambiente Controlado , Feminino , Genótipo , Hospitais Universitários , Humanos , Legionella pneumophila/genética , Masculino , Abastecimento de Água
SELEÇÃO DE REFERÊNCIAS
DETALHE DA PESQUISA
...